UNCLASSIFIED
TM-GEAR-011
MAST AND TOWER — PORTABLE AND FIXED INSTALLATIONS
Wind Load Calculations, Pneumatic Mast, Crank-Up Tower, Aluminum Telescoping
Chapter 1 — Introduction and Scope
This manual covers structural requirements and installation procedures for four antenna support types: aluminum telescoping push-up mast (10–12 m), pneumatic air mast (7–9 m, rapid deployment), crank-up tower (10–30 m, non-crank-up portable variant), and guyed vertical mast. Wind load calculations follow EIA/TIA-222-H and ASCE 7-22.
Chapter 2 — Theory of Operation
2-1 Wind Load Calculation
The design wind pressure is:
q (Pa) = 0.613 × V² (V in m/s) q (psf) = 0.00256 × V² (V in mph) Design defaults: Operational: 50 mph (22.4 m/s) → q = 308 Pa Operational max: 70 mph (31.3 m/s) → q = 600 Pa Survival: 90 mph (40.2 m/s) → q = 990 Pa
The force on a cylindrical mast section (vertical member):
F (N) = q × C_d × A C_d = 1.0 (cylinder drag coefficient) A = projected area = diameter (m) × height (m)
2-2 Guy Wire Tension
For a guyed mast, the overturning moment M = F × h/2. Guy wire tension T = M / (r × cosθ), where r = guy radius and θ = angle from horizontal. For 45° guys: T = M / (r × 0.707). Use 3:1 safety factor on all guy wire ratings.
Chapter 3 — Equipment and Materials
| Component | Telescoping | Pneumatic | Crank-Up |
|---|---|---|---|
| Sections | 6–8 × 1.5m Al tube | Fiberglass, 4 sections | Steel lattice, 3–6 |
| Material | 6061-T6 aluminum | Fiberglass tube | Galvanized steel |
| Guys | 3× at each level | None (self-supporting to 9m) | 3× per section |
| Guy wire | 1/4″ Phillystran or Dacron | — | 3/16″ EHS steel |
| Anchors | Screw anchors, 500 kg | — | Concrete deadman |
| Base | Tripod or plate, 0.6m | Plate, 0.3m | Concrete base, 1m |
Chapter 4 — Construction and Erection
4-1 Telescoping Mast Erection
- Install the base plate on level ground. Anchor with 4×screw anchors or 4×250 kg sandbags in field operation.
- Extend sections one at a time, starting from the bottom. Tighten each section clamp before extending the next.
- Install guys at three levels: 1/3, 2/3, and top of full height. Guy radius must be ≥40% of height (rule of thumb); recommended 60%.
- Tension all guys evenly. Mast vertical alignment: check with a plumb bob from the top. Adjust guys until mast is plumb to within 1°.
4-2 Pneumatic Mast
- Extend collapsed mast horizontally. Connect air supply (bicycle pump, foot pump, or compressor) to the base Schrader valve.
- Pump to 2.5–3.5 bar (36–51 psi). The sections extend sequentially from top to bottom. Full extension: approximately 60 pump strokes with a standard floor pump.
- Once extended, set upright. Install base plate or drive the ground spike. Pneumatic masts are self-supporting to 9 m with no antenna wind load; add guys for wind exposure or antenna weight >2 kg.
Chapter 5 — Operating Procedures
- Never erect a mast within fall distance of power lines. Required clearance: mast height + 3 m.
- For portable operation, lower the antenna before moving the mast. Telescoping sections must be collapsed before transport; partially extended masts have the lowest collapse load capacity.
- Inspect all guy wire attachment points before each use. Replace any guy wire showing kinks, broken strands, or corrosion at terminations.
- In winds exceeding 50 mph: lower the antenna or lower the mast entirely if the design survival wind speed is less than the forecast wind.
Chapter 6 — Calibration
- Measure actual mast height with a measuring tape or laser rangefinder. Record height at each clamp position for future reference.
- Verify guy wire tension: each guy in a set of three should be tensioned equally. Use a wire tension gauge; target 10–15% of rated breaking strength for operational tension.
- Plumb verification: with all guys tensioned, measure horizontal offset at the top with a plumb line. Must be <1% of mast height.
Chapter 7 — Verification and Acceptance
- Mast plumb within 1% of height (e.g., <0.1 m offset for a 10 m mast).
- All guy wires tensioned and attachment hardware secure (no loose turnbuckles, no shackle pins without cotter pins).
- Wind load calculation completed and documented for the installed configuration (mast height, antenna size, design wind speed).
- Log: date, mast type, height, antenna mounted, guy radius, design wind speed, tension measurements, operator.
Appendix A — Worked Wind Load Example
10 m aluminum mast, 50 mm OD, at 70 mph (31.3 m/s):
q = 0.613 × 31.3² = 0.613 × 979 = 600 Pa A = 0.050 m × 10 m = 0.50 m² F = 600 × 1.0 × 0.50 = 300 N (67 lbf) on the mast alone Add 2-element Yagi (projected area ~0.5 m²) at top: F_antenna = 600 × 1.2 × 0.50 = 360 N Total F = 300 + 360 = 660 N (148 lbf) Overturning moment M = 660 × 5 m = 3300 N·m (mast + antenna CG) Guy wire tension (3 guys, 45° angle, 6 m radius): T = 3300 / (6 × 0.707 × 2/3) = 3300 / 2.83 = 1166 N per guy Use 1/4" Phillystran (rated 2200 N) with 3:1 safety factor.
Appendix B — Mast Tube Wall Thickness Reference
| OD (mm) | Wall (mm) | Max height (unguyed) | Max height (1 set guys) |
|---|---|---|---|
| 32 | 2.0 | 4 m | 6 m |
| 38 | 2.5 | 5 m | 8 m |
| 50 | 3.0 | 6 m | 10 m |
| 63 | 3.5 | 8 m | 12 m |